Manual Fixed Fire Water Cannons
The cannon’s operational logic is fully optimized for real-world efficiency, with core components including a rotational/pitching mechanism, flow-adjustable nozzle, and pressure monitoring system: Angle Adjustment: The stainless steel handle enables 360° horizontal rotation and -30° to +70° vertical adjustment, covering a circular area with a 50-meter radius (≈7,850 m²) without repositioning. Mode Switching: The segmented nozzle changes flow area by rotating the outer sleeve—with a contraction ratio of 1:4 in direct jet mode and 1:2 in spray mode, enabling precise control of flow and jet shape. Pressure Verification: The built-in pressure gauge displays network pressure in real time. When pressure drops below 0.3 MPa, range decreases by over 30%, requiring immediate activation of backup pumps—directly aligning with the mandatory requirement in Code for Fire Water Supply and Hydrant Systems (GB 50974-2014) that "dynamic pressure at fire water cannons shall not be less than 0.3 MPa."
Description
Ca-Fire Protection Co.,Ltd is one of the most credible manufacturers and suppliers of manual fixed fire water cannons in China. Welcome to wholesale custom made fire equipment products at competitive price from our factory. Contact us for more cheap products.
Products Description

Manual Fixed Fire Water Cannons
1. Precise Calculation of Flow and Range
The flow rate and range of a water cannon are not fixed values but follow the fluid dynamics formula:Q=K×Pwhere Q is the flow rate (L/s), K is the flow coefficient (related to nozzle structure), and P is the inlet pressure (MPa). The segmented Venturi nozzle of this cannon gives it a K-factor of 80–120. At 1.0 MPa, it delivers a flow rate of 80–120 L/s, with a direct jet range of 50–60 meters-5–8 times that of a standard fire hydrant nozzle (5–15 L/s).
2. Fluid Dynamics of Dual Jet Modes
Direct Jet Mode: The nozzle's convergent section compresses water into a dense column, minimizing air resistance and maximizing range, ideal for long-distance suppression of Class A (solid fuel) fires.
Spray Mode: Rotating the outer sleeve redirects water to strike internal deflectors, creating fine water mist with droplet sizes of 100–1000 μm. This mist has 3–5 times the cooling efficiency of a direct jet, making it suitable for explosion-proof cooling in chemical scenarios (Class B and C fires).
3. Material Engineering for Pressure and Corrosion Resistance
The main body is cast from ductile iron QT450-10, with a yield strength ≥ 300 MPa and a rated working pressure of 1.6–2.5 MPa, enabling it to withstand transient water hammer impacts (2–3 times the working pressure) during pump startup. The nozzle is made of glass-fiber-reinforced PA66 engineering plastic, with a heat deflection temperature ≥ 220°C, maintaining toughness at -40°C to 80°C for extreme climate use.
Multi-Scenario Fire Safety Value
1. Large-Space Buildings: Filling Hydrant Coverage Gaps
In logistics parks and exhibition centers with ceilings >8 meters, standard hydrant nozzles only reach 10–15 meters, failing to cover cross-area fire points. The 50–60 meter range of the water cannon enables "single-point coverage of multiple zones," with 360° rotation allowing one cannon to protect an entire fire compartment, reducing equipment redundancy.
Professional Knowledge Extension: The heat release rate (HRR) in large-space fires can be 10 times higher than in ordinary buildings. The cannon's high-flow jet rapidly reduces fire temperature, aligning with the tactical principle of "containment first, rescue prioritized."
2. Chemical Parks: Core Equipment for Explosion-Proof Cooling
In chemical tank farms, direct jet attacks on flammable liquid fires can cause splashing and spread. The cannon's spray mode creates a mist layer ≥0.5 meters thick, cooling tank surfaces at ≥10°C/min to prevent explosions and diluting surrounding combustible gases below their lower explosive limit (LEL).
Professional Knowledge Extension: Per Code for Design of Fire Protection in Petrochemical Enterprises (GB 50160-2008), water cannons in tank farms must be spaced ≤60 meters apart with a protection radius ≥50 meters to ensure full coverage.
3. Outdoor Freeze Protection: Winter Network Defense in Northern China
In northern China's severe cold regions, frozen outdoor fire equipment is a leading winter failure. This cannon features a built-in DN25 drain valve to empty residual water before winter, and with a self-regulating heating trace (≥100W/m), it operates reliably at -20°C, avoiding freeze-related failure.
Professional Knowledge Extension: Winter fire safety in northern China centers on "freeze protection and unobstructed flow." The cannon's drain valve must be linked with network drain valves to fully empty residual water-a process mandated in GB 50974's winter maintenance guidelines.

Safety Guidelines for Installation and Maintenance
Installation Requirements
Location: Install in unobstructed, high-visibility positions, 3–5 meters above ground to ensure coverage of the most unfavorable point. In chemical parks, maintain ≥15 meters from tanks to avoid damage from blast waves.
Pressure Compatibility: Supply pipes must be ≥DN100 with head loss ≤0.1 MPa/100m to meet flow demands. System pressure must stay within 0.3–1.2 MPa to prevent nozzle rupture or reduced range.
Labeling: Post clear operation instructions nearby, detailing "direct/spray switching" and "pressure anomaly procedures" for emergency use by non-professionals.
Maintenance Protocols
Monthly Inspections: Check rotational/pitching mechanisms for stiffness; use an endoscope to clear nozzle debris; calibrate pressure gauges every 6 months to ensure ≤±2% accuracy.
Quarterly Pressure Testing: Activate fire pumps to verify range and flow at 0.3 MPa, ensuring mode switching is smooth and flow deviation ≤±5%.
Annual Integration Testing: Conduct joint tests with fire alarm systems to confirm response time ≤30 seconds and compliance with code requirements.
Winter Special Maintenance: Fully drain residual water before winter and install insulation jackets; inspect heating trace operation weekly to prevent freezing.
FAQ
Q: What is Foreign Trade-Express?
A: Foreign Trade Express is a one-stop intelligent foreign trade network marketing SaaS system platform.
Q: Can you accept OEM?
A: Yes, we do customized design for our clients.
Q: Are you manufacturer with your own factory?
A: Yes, we are the manufacturer for more than 20 years,our factory produce the fire sprinkler and fire foam products,welcome to visit anytime.
Q: Can I visit Slion factory ? Can your factory arrange transportation to us ?
A: Yes,It's great honner to invite you to visit Slion .We can pick you up from wenling station.It's about 50 minutes from station to our factory.
Q: Which areas do you export ?
A: Europe,USA,North america,South America,Middle east,Asia and Africa.
Our address
NO.8, YUANFENG ROAD, MEIYUAN VILLAGE, KANGMEI TOWN, NANAN CITY, QUANZHOU CITY, FUJIAN CHINA
+86 15880910562
sales7@ca-fire.com

Hot Tags: manual fixed fire water cannons, China manual fixed fire water cannons manufacturers, suppliers, factory
Send Inquiry
You Might Also Like