CA-FIRE PSKD Series Fixed Electrically Controlled Fire Monitor Product
CA-FIRE PSKD Series Fixed Electrically Controlled Fire Monitor Product Introduction For PSKD Series Fixed Electrically Controlled Fire Monitor (Models: PSKD8/20W, PSKD8/30W, PSKD8/40W, PSKD8/50W, PSKD8/60W, PSKD10/80W) 0. Company Introduction CA-FIRE Fire Protection Co., LTD, founded in 2012 and...
Description
Ca-Fire Protection Co.,Ltd is one of the most credible manufacturers and suppliers of ca-fire pskd series fixed electrically controlled fire monitor product in China. Welcome to wholesale custom made fire equipment products at competitive price from our factory. Contact us for more cheap products.
CA-FIRE PSKD Series Fixed Electrically Controlled Fire Monitor Product Introduction
For PSKD Series Fixed Electrically Controlled Fire Monitor (Models: PSKD8/20W, PSKD8/30W, PSKD8/40W, PSKD8/50W, PSKD8/60W, PSKD10/80W)
0. Company Introduction
CA-FIRE Fire Protection Co., LTD, founded in 2012 and located in Quanzhou, China, specializes in the research, development, and manufacturing of high-quality firefighting equipment. Our product portfolio covers FM-certified fire sprinklers, hydrants, alarm valves, foam systems, and CCC/CE-certified nozzles. We are committed to delivering dependable, long-lasting, and compliant fire safety solutions for residential, commercial, and industrial properties across the globe.CA-FIRE's product range caters to diverse fire protection demands, including Fire Sprinklers; Indoor & Outdoor Fire Hydrants; Alarm Valves (Wet/Deluge/Explosion-Proof Types); Foam Systems (Bladder Tanks, Generators); Fire Nozzles, Water Monitors & Hoses; Hose Reels, Couplings & Accessories; and Electrically Controlled Fire Monitors (Fixed Type). Every product undergoes rigorous quality control and adheres to GB19156-2019 standards, with customizable sizes and solutions available to fit specific project needs.
1. Product Overview & Core Advantages
1.1 Product Overview
The PSKD Series Fixed Electrically Controlled Fire Monitor is an intelligent fire extinguishing and cooling device that achieves directional spraying via electric control. It supports electric switching between direct jet and spray modes through a nozzle-mounted motor-enabling long-distance targeted suppression and short-range wide-area coverage. With an IP65 outdoor rainproof protection rating, it features a simple structure, stable performance, flexible electric operation, and convenient maintenance. Compatible with water and aqueous film-forming foam, it is widely applied to airports, warehouses, ports and docks, ships, fire-fighting vessels, offshore fixed platforms, and fire trucks-providing efficient, remote-controllable fire protection for high-risk and large-scale environments.
1.2 Core Advantages
Electric Control & Dual Spraying Modes: Electrically adjustable between direct jet (long-distance) and spray (wide coverage) modes; operated via on-site control box or remote controller for flexible, labor-saving operation.
Superior Range Performance: 射程 ranges from ≥50m to ≥85m (varies by model), with optimal range at 30° vertical angle-enabling safe, long-distance fire suppression.
Outdoor Durability: IP65 protection rating ensures rainproof and dustproof performance, suitable for harsh outdoor and offshore environments.
Wide Motion Coverage: ≥350° horizontal rotation and -15°~+60° pitching range cover almost all directions; maximum spray angle ≥90° for broad coverage.
Dual-Medium Compatibility: Works with water and aqueous film-forming foam, adapting to solid, liquid, and flammable liquid fires.
Stable & Low-Maintenance: Simple structure with reliable performance; only regular lubrication and blockage checks required, reducing operational costs.
2. Technical Specifications
| Specification Category | Details |
|---|---|
| Model Series | PSKD8/20W, PSKD8/30W, PSKD8/40W, PSKD8/50W, PSKD8/60W, PSKD10/80W |
| Spray Medium | Water, Aqueous film-forming foam |
| Flow Rate | PSKD8/20W:20L/s; PSKD8/30W:30L/s; PSKD8/40W:40L/s; PSKD8/50W:50L/s; PSKD8/60W:60L/s; PSKD10/80W:80L/s |
| Rated Working Pressure | PSKD8 Series: 0.8MPa, 1.0MPa; PSKD10/80W: Consistent with series standard |
| Maximum Working Pressure | 1.6MPa (all models) |
| Spray Range | PSKD8/20W:≥50m; PSKD8/30W:≥60m; PSKD8/40W:≥65m; PSKD8/50W:≥70m; PSKD8/60W:≥75m; PSKD10/80W:≥85m |
| Horizontal Rotation Angle | ≥350° |
| Pitching Range | Minimum Depression: <-15°; Maximum Elevation: ≥+60° |
| Maximum Spray Angle | ≥90° |
| Protection Class | IP65 (rainproof, dustproof) |
| Operating Mode | Electric control (on-site control box + remote controller) |
| Executive Standard | GB19156-2019 |
| Certifications | CCC, CE |
3. Installation, Operation & Maintenance Guidelines
3.1 Installation Requirements
Install the fire monitor base on a pipeline equipped with an electric valve-ensure the pipeline is pressure-tested, flushed, and unobstructed before installation.
Verify the installation base has sufficient anti-impact capacity to withstand swinging force and recoil during spraying, preventing misrotation.
Ensure the control box and wiring are protected from water and dust; follow electrical safety standards for wiring connections.
Confirm the installation position provides a clear spray path, with no obstacles blocking the nozzle's rotation or spraying range.
3.2 Operation Steps
Pre-Fire Preparation: Ensure the electric valve is closed; check the control box/remote controller for normal operation and the fire monitor for unobstructed rotation.
Target Positioning: Use the on-site control box or remote controller to adjust the fire monitor's horizontal and vertical angles, aligning the nozzle with the fire source.
Mode Selection: Electrically switch between direct jet (for long-distance suppression) and spray (for short-range wide coverage) modes based on fire size and distance.
Start Spraying: Open the electric valve to initiate spraying; for optimal range, set the nozzle's vertical angle to 30° (adjust as needed for actual conditions).
Post-Fire Shutdown: After extinguishing the fire, close the electric valve, switch the spray mode to standby, and reset the fire monitor to the default position.
3.3 Maintenance Tips
Regular Lubrication: Inject lubricating grease into the steel ball grooves periodically to ensure flexible rotation of the gun body.
Blockage Inspection: If spraying pressure is abnormally high or range is significantly reduced, inspect the nozzle and internal channels for blockages-remove debris promptly to restore performance.
Surface Protection: For long-term outdoor or offshore use, apply anti-corrosion treatment to the monitor surface to resist rust and environmental damage.
Electrical Component Check: Regularly inspect the control box, wiring, and motor for water damage or loose connections; replace damaged components immediately to ensure electric control reliability.
3.4 Precautions
Never stand in front of the nozzle during operation to avoid accidents caused by high-pressure spray impact.
Ensure the installation base is firmly fixed and has sufficient load-bearing capacity-recoil and swinging force during spraying may cause displacement if the base is unstable.
Use only compatible media (water or aqueous film-forming foam); avoid using corrosive substances that may damage internal components.
Protect the control box and remote controller from extreme temperatures and humidity to maintain electrical performance.
4. Packaging & Transportation
Our PSKD Series Electrically Controlled Fire Monitors are packaged in export-grade wooden crates with shock-absorbing foam to protect the gun body, nozzle, and electrical components. This packaging ensures stability during transit, prevents damage from handling or impact, and guarantees the product arrives in pristine condition with intact functionality and IP65 protection.
5. Application Scenarios
Transportation Hubs: Airports, ports, docks, and railway freight yards.
Industrial & Storage Facilities: Large warehouses, logistics centers, and petrochemical storage tank farms.
Marine & Offshore: Ships, fire-fighting vessels, offshore oil platforms, and coastal protection facilities.
Emergency Services: Fire trucks and mobile fire suppression units requiring remote control.
Public & Commercial Spaces: Large stadiums, exhibition centers, and high-risk industrial parks.
6. Frequently Asked Questions (FAQ)
Q: What spray media are compatible with this fire monitor?A: It works with water and aqueous film-forming foam, suitable for suppressing solid combustible fires and flammable liquid fires.
Q: How is the fire monitor controlled?A: It supports dual control modes-on-site control box for local operation and remote controller for long-distance adjustment, enabling flexible use in different scenarios.
Q: What is the optimal angle for maximum spray range?A: The longest range is achieved when the nozzle's vertical angle with the ground is 30°; adjust the angle based on the fire's distance and spread.
Can it be used outdoors in rainy weather?A: Yes. It has an IP65 protection rating, which is rainproof and dustproof, making it suitable for long-term outdoor installation and use.
Q: How often should the fire monitor be maintained?A: Inject lubricating grease every 3 months; check for blockages and electrical component integrity monthly. For harsh environments (e.g., offshore), increase maintenance frequency.
7. Product Comparison (vs. Competitors & Manual Fire Monitors)
| Key Comparison Points | CA-FIRE PSKD Series Electrically Controlled Monitor | Competitor Electric Monitor | CA-FIRE PL30 Manual Monitor |
|---|---|---|---|
| International Certifications | CCC + CE + GB19156-2019 | CE Only | CCC + CE |
| Control Mode | Electric (on-site + remote) | On-site Electric Only | Manual (handle) |
| Spray Modes | Direct Jet + Spray (electric switch) | Direct Jet Only | Direct Jet Only |
| Protection Class | IP65 (outdoor-resistant) | IP54 | No Special Protection |
| Spray Range | Up to ≥85m | Up to ≥60m | ≥60m |
| Rotation & Pitching | 350° + (-15°~+60°) | 320° + (-10°~+50°) | 360° + (-60°~+90°) |
| Anti-Impact Capacity | High (requires reinforced base) | Medium | Medium |
| Annual Maintenance Cost | $30/Unit (electrical + mechanical) | $50/Unit (frequent electrical failures) | $20/Unit (mechanical only) |
| After-Sales Warranty | 2 Years + Electrical Component Guarantee | 1 Year | 2 Years |
8. Contact: Dulcia
Email: sales8@ca-fire.com
Tel/WhatsApp: +86 191 6381 1547
WeChat: Dulcia8
Hot Tags: ca-fire pskd series fixed electrically controlled fire monitor product, China ca-fire pskd series fixed electrically controlled fire monitor product manufacturers, suppliers, factory
Send Inquiry
You Might Also Like