CA-FIRE ZSJZ Type Water Flow Indicator Product Introduction For ZSJZ Series Saddle-Type Water Flow Indicator (Models: ZSJZ 50-M-1.6 to 200-M-1.6) 0. Company Introduction CA-FIRE Fire Protection Co., LTD, founded in 2012 and located in Quanzhou, China, specializes in the R&D, manufacturing,...
Description
Ca-Fire Protection Co.,Ltd is one of the most credible manufacturers and suppliers of ca-fire zsjz type water flow indicator product in China. Welcome to wholesale custom made fire equipment products at competitive price from our factory. Contact us for more cheap products.
CA-FIRE ZSJZ Type Water Flow Indicator Product Introduction
For ZSJZ Series Saddle-Type Water Flow Indicator (Models: ZSJZ 50-M-1.6 to 200-M-1.6)
0. Company Introduction
CA-FIRE Fire Protection Co., LTD, founded in 2012 and located in Quanzhou, China, specializes in the R&D, manufacturing, and supply of high-quality firefighting equipment. Our product portfolio covers FM-certified fire sprinklers, alarm valves, dry/wet fire hydrants, foam systems, CCC/CE-certified nozzles, CCCF-certified lined fire hoses, and water flow indicators. We adhere to strict national and international standards (e.g., GB 5135.7-2018) and deliver reliable fire safety solutions for residential, commercial, industrial, and public facilities worldwide.
CA-FIRE's product range caters to diverse fire protection needs, including Fire Sprinklers & Accessories; Alarm Valves (Wet/Deluge/Explosion-Proof Types); Dry/Wet Fire Hydrants; Foam Extinguishing Systems; Fire Nozzles, Water Monitors & Hoses; Lined Fire Hoses; and Water Flow Indicators. All products undergo rigorous factory testing and third-party certification, ensuring compliance with local regulations and project acceptance requirements.
1. Product Overview & Core Advantages
1.1 Product Overview
The ZSJZ Type Water Flow Indicator is a critical alarm component for automatic sprinkler fire extinguishing systems, designed to convert water flow signals into electrical signals for real-time fire alerts. Compliant with GB 5135.7-2018 《Automatic Sprinkler Fire Extinguishing System - Part 7: Water Flow Indicator》, it features a saddle-type connection and rubber sensing component for sensitive and reliable operation. Widely used in medium and light hazard buildings-hotels, shopping malls, restaurants, entertainment venues, hospitals, office buildings, factories, and warehouses-it triggers alarms when water flow reaches 15~37.5 L/min, helping quickly locate fire-affected areas.
The indicator consists of a body, paddle, rubber sensing component, micro switch, and nameplate box. Its saddle-type design allows easy installation on existing pipelines (via pipe opening), and the rubber sensor ensures durable performance. With a rated working pressure of 1.6MPa and water test pressure of 3.2MPa, it withstands the pressure demands of sprinkler systems.
1.2 Core Advantages
Standard Compliance: Fully meets GB 5135.7-2018 national standards, ensuring qualification for domestic and international projects.
Precise Sensitivity: Triggers alarms at 15~37.5 L/min; no false alarms when flow ≤15 L/min, ensuring accurate fire detection.
Flexible Installation: Saddle-type connection supports on-site pipe opening installation; can be installed vertically (preferred) or adjusted for non-vertical setups with sensitivity verification.
Robust Pressure Bearing: Water test pressure of 3.2MPa (2× rated pressure) guarantees leak-proof performance and structural integrity.
Easy Operation & Maintenance: Factory-calibrated sensitivity (no user adjustment needed); simple half-yearly inspections ensure long-term reliability.
Wide Compatibility: Available in 7 models (DN50~DN200) to fit different pipeline sizes in sprinkler systems.
Durable Components: Rubber sensing component and corrosion-resistant body ensure stable operation in humid environments.
2. Technical Specifications
2.1 Core Performance Parameters
| Specification Category | Details |
|---|---|
| Model Series | ZSJZ 50-M-1.6, ZSJZ 65-M-1.6, ZSJZ 80-M-1.6, ZSJZ 100-M-1.6, ZSJZ 125-M-1.6, ZSJZ 150-M-1.6, ZSJZ 200-M-1.6 |
| Compliance Standard | GB 5135.7-2018 |
| Connection Type | Saddle-type |
| Sensing Component | Rubber |
| Rated Working Pressure | 1.6MPa |
| Water Test Pressure | 3.2MPa |
| Sensitivity Range | Alarm: 15~37.5 L/min; No alarm: ≤15 L/min |
| Electrical Parameters | DC 24V 1A; AC 220V 0.5A |
| Installation Orientation | Vertical (preferred); Non-vertical (with sensitivity check) |
| Storage Temperature | -10℃~40℃ |
| Certifications | CCC, GB 5135.7-2018 compliant |
2.2 Pipe Opening & Connection Dimensions (mm)
| Model | Pipe Opening Size (Φ) |
|---|---|
| ZSJZ 50-M-1.6 | 42 |
| ZSJZ 65-M-1.6 | 50 |
| ZSJZ 80-M-1.6 | 50 |
| ZSJZ 100-M-1.6 | 50 |
| ZSJZ 125-M-1.6 | 50 |
| ZSJZ 150-M-1.6 | 50 |
| ZSJZ 200-M-1.6 | 84 |
3. Installation, Debugging & Maintenance Guidelines
3.1 Installation Requirements
Pipeline Preparation: Install on straight pipe segments with length ≥5× pipe diameter (front and rear) to ensure accurate flow sensing.
Direction Alignment: Ensure the arrow on the indicator matches the water flow direction; incorrect orientation causes failure to trigger.
Paddle Handling: Roll the sensing paddle into a cylindrical shape when inserting into the pipe; use the same method for disassembly to avoid damage.
Vertical Installation: Preferred vertical mounting with the pipeline; if non-vertical installation is necessary, verify sensitivity post-installation.
Wiring: Follow the wiring diagram to connect the electrical signal (compatible with DC 24V/1A and AC 220V/0.5A systems).
Saddle-Type Installation: Open the pipe according to instructions for saddle-type mounting; ensure a tight seal to prevent leakage.
3.2 Debugging & Operation
Post-Installation Check: Verify no burrs, welding slag, or debris in the pipeline (these can jam the paddle).
Sensitivity Verification: Test with water flow-confirm no alarm at ≤15 L/min and reliable alarm at 15~37.5 L/min.
Factory Calibration: Sensitivity is pre-adjusted at the factory; do not re-adjust unless necessary (follow sensitivity requirements if adjustment is needed).
3.3 Maintenance & Troubleshooting
3.3.1 Regular Maintenance
Conduct half-yearly inspections: Check paddle movement, wiring connections, and sensor integrity; clean debris from the pipeline if needed.
3.3.2 Common Faults & Solutions
| Fault | Cause | Troubleshooting |
|---|---|---|
| No signal output (no action) | Paddle misinstalled/stuck on pipe wall | Adjust the paddle position for free movement |
| Pipeline debris (burrs, welding slag) jamming the paddle | Remove debris from the pipeline | |
| Incorrect installation direction | Realign to match water flow (arrow direction) | |
| Unreliable action | Mismatched paddle specifications | Replace with the correct paddle model |
| No reset/improper reset | Misadjusted reset screw | Adjust the reset screw to restore proper reset function |
4. Packaging & Transportation
Packaging: Each water flow indicator is individually fixed in a carton to avoid collision; each package includes a certificate of conformity, instruction manual, and packing list. Cartons are marked with placement direction and moisture-proof labels.
Transportation: Prevent shock during transit; avoid dropping, throwing, or colliding during loading/unloading.
Storage: Store in a ventilated, dry warehouse (-10℃~40℃); avoid storing with corrosive substances.
5. Application Scenarios
Commercial Buildings: Hotels, shopping malls, restaurants, entertainment venues, and office buildings.
Public Facilities: Hospitals, schools, community centers, and railway stations.
Industrial & Logistics: Factories, warehouses, and logistics centers (medium and light hazard).
Residential Buildings: High-rise apartments, villa complexes, and residential underground garages.
Infrastructure: Subway stations, underground passages, and public parking garages.
6. Frequently Asked Questions (FAQ)
Q: What standard does this water flow indicator comply with?A: It fully complies with GB 5135.7-2018 《Automatic Sprinkler Fire Extinguishing System - Part 7: Water Flow Indicator》, meeting national fire safety requirements.
Q: Can the sensitivity be adjusted by the user?A: It is factory-calibrated, so users generally do not need to adjust it. If adjustment is necessary, follow the sensitivity range (15~37.5 L/min) for calibration.
Q: What pipeline length is required for installation?A: It must be installed on straight pipe segments with length not less than 5 times the pipe diameter (front and rear) to ensure accurate flow sensing.
Q: Is vertical installation mandatory?A: Vertical installation is preferred, but non-vertical installation is allowed-just verify the sensitivity after installation to ensure it meets requirements.
Q: What electrical systems is it compatible with?A: It supports both DC 24V 1A and AC 220V 0.5A electrical systems, adapting to different sprinkler system configurations.
7. Product Comparison (vs. Competitors)
| Key Comparison Points | CA-FIRE ZSJZ Type Water Flow Indicator | Competitor A | Competitor B |
|---|---|---|---|
| Compliance Standard | GB 5135.7-2018 + CCC | GB 5135.7-2018 Only | No Formal Standard |
| Sensitivity Range | 15~37.5 L/min (precise) | 20~40 L/min (wide) | 10~30 L/min (prone to false alarms) |
| Water Test Pressure | 3.2MPa (2× rated) | 2.4MPa (1.5× rated) | 2.0MPa (1.25× rated) |
| Installation Flexibility | Saddle-type (pipe opening + vertical/non-vertical) | Flange-type (fixed installation) | Saddle-type (vertical only) |
| Maintenance Frequency | Half-yearly | Quarterly | Monthly |
| Component Durability | Rubber sensor (anti-aging) | Ordinary plastic sensor | Rubber sensor (short service life) |
| After-Sales Warranty | 2 Years | 1 Year | No Warranty |