Application Of Deluge Valve
The deluge valve adopts professional fluid 3D design, diaphragm is made of high quality double sandwich reinforced rubber material, spring is made of stainless steel, valve body and valve cover are made of ductile iron.
Description
Ca-Fire Protection Co.,Ltd is one of the most credible manufacturers and suppliers of application of deluge valve in China. Welcome to wholesale custom made fire equipment products at competitive price from our factory. Contact us for more cheap products.
Application Of Deluge Valve
Application of deluge valve:When installing the system, it should be carried out in accordance with GB50261-96. The main water supply signal butterfly valve, rain valve, solenoid valve, etc. are concentrated in the control room near the protection area, the indoor temperature should not be lower than 4°C, so as to avoid freezing affecting the system function, and the control room should not be too far away, so as to avoid the occurrence of fire, etc., because the rain valve pipe network is too long resulting in watering delay.
ZSFM diaphragm rain valve should be installed vertically, the height from the ground should be 1.2M, the distance from the wall on both sides should be not less than 0.5M, and the front distance from the wall is 1.2m. The signal butterfly valve is set within 1-2M behind the valve for system debugging. When connecting the signal butterfly valve, open the plastic cover and connect the 24V power supply to the red line of the patch board, and connect the yellow line (or blue line together) to the fire control center as the output signal. After the wiring is complete, the handwheel can be rotated to check whether the signal output is open and close.
Floor drains should be set in the drainage areas of the system water discharge valve, manual quick opening valve, solenoid valve, hydraulic alarm bell, etc., so that the discharge water flows into the sewer respectively. The diameter of the drainage pipe should not be less than 2 times of the matching diameter of the rain shower valve.
The hydraulic fluid should be located in the main channel of the building or near the place where people often stay, the pipe diameter is 20mm, and the total length of the pipe should not be greater than
20m, the height from the alarm valve should not be greater than 5m.
The number of sprinkler heads installed in each shower valve of the automatic sprinkler system should be determined by hydraulic calculation, and the water flow rate in the pipeline should be guaranteed to be 5-lOm/s.
After the installation is complete, you can close the signal butterfly valve after the valve, open the water discharge valve, and then open the solenoid valve or manual quick opening valve, so that the diaphragm pressure chamber pressure relief, the rain valve open. Water is discharged from the drain valve.
After the system is put into normal operation, it must be maintained and checked according to the regulations, and the opening of the signal butterfly valve should be checked frequently. The solenoid valve should be checked monthly and should be tested for start-up. When the operation is abnormal, it should be replaced in time.