Warehouse Fire Sprinkler System: Warehouses are places where goods are stored in a centralized manner. Due to the high stacks, dense cargo, and high fire load (especially Class C flammable solid/liquid warehouses), fires spread quickly and are difficult to extinguish. The selection, layout, and installation of fire sprinklers directly determine the effectiveness of the fire extinguishing system.

Description

Ca-Fire Protection Co.,Ltd is one of the most credible manufacturers and suppliers of warehouse fire sprinkler system in China. Welcome to wholesale custom made fire equipment products at competitive price from our factory. Contact us for more cheap products.

 

Products Description

product-800-800

 

Warehouse Fire Sprinkler System

Warehouse Fire Sprinkler System: Warehouses are places where goods are stored in a centralized manner. Due to the high stacks, dense cargo, and high fire load (especially Class C flammable solid/liquid warehouses), fires spread quickly and are difficult to extinguish. The selection, layout, and installation of fire sprinklers directly determine the effectiveness of the fire extinguishing system.

 

Key requirements for installation Warehouse Fire Sprinkler System

 

 

 

ESFR sprinklers:
Installation Height: The vertical distance between the sprinkler deflector and the top of the stack must be ≥ 0.9 m and ≤ 1.5 m (to prevent water flow from being blocked by flames).
Spacing: ≤ 3.7 m for single-row installations and ≤ 4.6 m for double-row installations. Avoid obstruction by cargo (no obstructions within 0.6 m of the sprinkler).
Water Supply Pressure: The pressure at the sprinkler must be ≥ 0.34 MPa (K = 161) at the most unfavorable point to ensure the flow rate meets the standard.
Regular sprinklers and in-rack sprinklers:
In-rack sprinklers must be installed sideways, ≤ 0.15 m from the rack crossbar, and spaced ≤ 3 m apart.
The top sprinkler deflector must be 75-150 mm from the top plate. For stacking heights greater than 3.5 m, additional sprinklers must be installed above the rack aisles. Other:
No goods should be stacked in the warehouse to block the sprinkler heads (the horizontal distance from the sprinkler heads should be ≥ 0.5 meters).
Steel racks must be fireproofed to prevent deformation from high temperatures that could cause sprinkler failure.

 

 

Warehouse fire risk characteristics

 

 

The stacking height is high (commonly 6-12 meters, and some high-bay warehouses can reach 20 meters). The hot smoke generated by the fire is prone to "thermal stratification", and ordinary sprinklers may fail due to temperature hysteresis.

 

The types of cargo vary greatly (cardboard, plastic, wood, chemicals, etc.), and the burning rates vary greatly (for example, the heat release rate of a foam plastic fire is 3-5 times that of ordinary cargo).

 

The shelves are severely blocked, and the sprinkler water is easily blocked by the goods or shelves, affecting the fire extinguishing effect

 

Fire spreads quickly. A fire in a high-stack warehouse may take only 5-10 minutes from the initial start to full combustion, requiring sprinklers to provide "quick response + high flow coverage"

 