The Fixed Manual Fire Monitor is a versatile firefighting device for industrial and high-risk areas. It allows precise control of water or foam with spray and straight stream modes. The monitor supports horizontal rotation and vertical tilt, enabling long reach and flexible targeting. Durable and easy to operate, it ensures effective fire suppression and personnel safety.

Description

Ca-Fire Protection Co.,Ltd is one of the most credible manufacturers and suppliers of manual fixed fire monitor in China. Welcome to wholesale custom made fire equipment products at competitive price from our factory. Contact us for more cheap products.

 

 

Products Description

 

product-800-800
 
 

CA-FIRE Manual Fixed Fire Monitor

This product is a Manual Fixed Fire Monitor-a core fire suppression device for large-space premises (e.g., large warehouses, steel structure factories, exhibition centers, stadiums) in industrial and civil buildings.

Compared to automatic fire monitors, manual fire monitors feature flexible operation, precise targeting, and low maintenance costs. They are ideal for areas with on-site personnel (who can respond quickly) and complex fire scenarios, serving as a key tool for initial fire suppression and large-scale fire control.

Core Technical Specifications

 

Item Technical Parameters (Models: PS3020W/PS3030W/PS3040W/PS10/50W) Fire Scenario Interpretation
Rated Flow Rate (L/S) 20 / 30 / 40 / 50 Higher flow rates cover larger areas: 20L/S for small Class A fires; 50L/S for medium Class B liquid fires
Rated Working Pressure (MPa) 0.8 / 0.8 / 0.8 / 1.0 Pressure determines jet range: 0.8MPa supports ≥50m effective range (meets most large-space needs)
Working Pressure Range (MPa) 0.5-1.6 (all models) Compatible with different fire pump pressure outputs: too low pressure reduces range; too high may damage seals
Effective Range (m) ≥50 / ≥50 / ≥65 / ≥70 Match range to space span: e.g., ≥50m range covers full 6m-high warehouses
Horizontal Rotation Angle 360° (all models) Manual operation enables 360° unobstructed coverage (avoid jamming of rotation mechanisms)
Vertical Rotation Angle +60°--70° (all models) Covers vertical range from ground fires to elevated equipment fires
Main Material Aluminum Alloy (all models) Lightweight for easy manual operation; corrosion-resistant and impact-resistant (suits damp/dusty fire environments)
Installation Method Seating Arrangement (all models) Fix to load-bearing structures; recommended installation height ≥2.5m (avoids accidental contact + expands coverage)
Connecting Flange DN100 (4 inches, all models) Fits standard fire pipeline diameters; ensure flange sealing during installation (prevents water leakage/ pressure loss)
Service Environment Temperature -10℃-+50℃ (all models) Take antifreeze measures (e.g., drain residual water) in low temperatures; high temperatures do not affect performance

Fire Safety Insights: Practical Value of Manual Fire Monitors

1. Fire Extinguishing Principle of Manual Fire Monitors

Fire monitors suppress fires via the cooling + smothering dual effects of high-pressure water flow:

Cooling: Water absorbs heat rapidly when contacting burning materials, lowering their temperature below the ignition point;

Smothering: Dense water flow isolates burning materials from oxygen, making it especially effective for Class A (solid) and Class B (liquid) fires.

2. Manual vs. Automatic Fire Monitors: How to Choose?

Scenario Type Recommended Equipment Reason
Staffed Factories/Warehouses Manual Fire Monitors On-site personnel can respond quickly; manual angle adjustment suits fires in complex storage areas (e.g., between shelves)
Unattended High-Space Venues Automatic Fire Monitors Relies on infrared/ultraviolet detection for automatic suppression (requires regular detection calibration)
Mixed Scenarios (Partially Staffed) Manual + Automatic Combination Balances precise manual operation (staffed areas) and automatic protection (unattended areas)

3. Initial Fire Suppression: 3-Step Manual Fire Monitor Operation

Start the Pump & Open the Valve: After detecting a fire, start the fire pump first, then open the pipeline control valve for the monitor (check the pressure gauge to ensure pressure stabilizes between 0.5-1.6MPa);

Aim Accurately: Hold the operating handle, adjust horizontal/vertical angles, and target the jet at the root of the fire (not the top of flames-root targeting is more efficient);

Sustained Jetting: After the fire is extinguished, continue jetting for 1-2 minutes (cool residual heat to prevent re-ignition).

 

Safe Operation Tips

Wear protective gloves during operation (to avoid hand scrapes from water flow recoil);

Do not approach the jet area when the monitor is in use (high-pressure water flow has strong impact and may cause injury);

Do not operate the monitor randomly outside of fire emergencies (to prevent abnormal pipeline pressure fluctuations).

product-800-800

FAQ

 

Q1: What environments are this fire monitor suitable for?
A1: It is ideal for high-risk areas such as oil and chemical plants, storage tank areas, airports, warehouses, and port facilities.

Q2: How do I switch between spray and straight stream modes?
A2: From the operator's position, rotate the nozzle handwheel clockwise for straight stream and counterclockwise for spray mode.

Q3: What safety precautions should I follow during operation?
A3: Always secure the base, hold the handle or handwheel firmly, and ensure correct alignment. Keep a safe distance and follow standard firefighting procedures.

Q4: Can the monitor rotate and tilt?
A4: Yes, it supports horizontal rotation of at least 180° and vertical tilt from -15° to +60°, allowing precise aiming and maximum coverage.

Q5: What are the recommended pressures and flow rates?
A5: Depending on the model, flow rates range from 30 to 80 L/s, with rated working pressures from 0.8 to 1.0 MPa and maximum pressure up to 1.6 MPa.

 

How To Cooperate With Us?
 

Our address

NO.8, YUANFENG ROAD, MEIYUAN VILLAGE, KANGMEI TOWN, NANAN CITY, QUANZHOU CITY, FUJIAN CHINA

 
WhatsApp

+86 15880910562

 

E-mail

sales7@ca-fire.com

product-943-596

 

Learn More

 

Hot Tags: manual fixed fire monitor, China manual fixed fire monitor manufacturers, suppliers, factory, Handwheel Control Fire Water Monitor For Fire Fighting, Stainless Steel Water Fire Monitor With Handheel, Handwheel Control Water Foam Fire Monitor, Handwheel Control Water Monitor, Fixed Firefighting Water Monitor, Stainless Steel Lever Control Fire Water Monitor

You Might Also Like

Shopping Bags