Home - News - Details

Key Points Of Construction And Installation Of Butterfly Valves

1. The installation position, height, and inlet and outlet direction must meet the design requirements, and the connection should be firm and tight. 2) All kinds of manual valves installed on the insulation pipeline, the handle shall not be downward.
2. The appearance inspection must be carried out before the valve installation, and the nameplate of the valve should comply with the provisions of the current national standard "General Valve Mark" GB 12220. For valves with working pressure greater than 1.0 MPa and cutting off on the main pipe, strength and strict performance tests should be carried out before installation, and they will be used only after they are qualified. During the strength test, the test pressure is 1.5 times the nominal pressure, the duration is not less than 5min, and the valve shell and packing should be qualified without leakage. During the tightness test, the test pressure is 1.1 times the nominal pressure; the test pressure should meet the requirements of GB 50243 standard during the duration of the test, and the valve disc sealing surface is qualified without leakage.