CA-FIRE ZSFZ(B) Type Wet Alarm Valve Product
CA-FIRE ZSFZ(B) Type Wet Alarm Valve Product Introduction For ZSFZ(B) Series Disc Type Wet Alarm Valve (ZSFZ(B) 80-1.6 to 300-1.6, ZSFZ(B) 100-1.6G to 200-1.6G) 0. Company Introduction CA-FIRE Fire Protection Co., LTD, founded in 2012 and located in Quanzhou, China, specializes in the research,...
Description
Ca-Fire Protection Co.,Ltd is one of the most credible manufacturers and suppliers of ca-fire zsfz(b) type wet alarm valve product in China. Welcome to wholesale custom made fire equipment products at competitive price from our factory. Contact us for more cheap products.
CA-FIRE ZSFZ(B) Type Wet Alarm Valve Product Introduction
For ZSFZ(B) Series Disc Type Wet Alarm Valve (ZSFZ(B) 80-1.6 to 300-1.6, ZSFZ(B) 100-1.6G to 200-1.6G)
0. Company Introduction
CA-FIRE Fire Protection Co., LTD, founded in 2012 and located in Quanzhou, China, specializes in the research, development, and manufacturing of high-quality firefighting equipment. Our products include fire sprinklers (FM certified), hydrants, alarm valves, foam systems, and nozzles (CCC and CE certified). We are committed to providing reliable, durable, and compliant fire protection solutions for residential, commercial, and industrial buildings worldwide.CA-FIRE specializes in high-quality fire protection equipment. We provide a wide range of products to meet diverse fire safety needs, including: Fire Sprinklers; Indoor and Outdoor Fire Hydrants; Alarm Valves, Wet and Deluge Valves; Foam Systems, Foam Bladder Tanks, and Foam Generators; Fire Nozzles, Water Monitors, and Fire Hoses; Hose Reels, Couplings, and Accessories; Valves and Signal Devices. All products are manufactured with strict quality control and meet international fire protection standards. Custom sizes and solutions are available to suit specific project requirements.
1. Product Overview & Core Advantages
1.1 Product Overview
The ZSFZ(B) Type Disc Type Wet Alarm Valve is a one-way valve that allows one-way water flow into sprinkler systems and triggers linked components to alarm at specified pressure and flow rates. It forms a widely used fixed fire extinguishing system with water flow indicators, pressure switches, and sprinklers, suitable for environments with ambient temperatures of 4℃~70℃. Compliant with GB50084-2017 "Design Specifications for Automatic Sprinkler Fire Extinguishing Systems" and GB5135-2003 standards, it is commonly installed in hotels, shopping malls, hospitals, cinemas, office buildings, high-rise buildings, warehouses, and underground garages. In standby mode, the system side is filled with working pressure water; when a fire occurs, sprinkler thermal elements burst, reducing system-side pressure. The valve flap opens under pressure difference to replenish water, while a small amount of water flows to the delay device and hydraulic alarm-triggering sound alerts and activating the fire pump via the pressure switch for efficient fire suppression.
1.2 Core Advantages
Stable & Reliable Performance: Precision manufacturing and high-quality materials ensure stable operation, small head loss, and sensitive activation, minimizing false alarms.
Broad Standard Compliance: Meets GB50084-2017 and GB5135-2003 standards, combined with CCC and CE certifications, ensuring global market access and project acceptance.
Multiple Specifications: Available in 10 models (80-1.6 to 300-1.6, 100-1.6G to 200-1.6G) with diverse calibers, adapting to different pipeline and system flow requirements.
Simple Maintenance: Easy-to-clean components and replaceable rubber seals reduce long-term operational costs; no complex disassembly required for routine maintenance.
Integrated Alarm Function: Seamlessly links with hydraulic alarm bells, pressure switches, and water flow indicators, enabling timely fire location and rapid response.
2. Technical Specifications
2.1 Overall Dimensions (mm)
| Model | h | H | A | B | M | N | K (Φ) | N-L | C |
|---|---|---|---|---|---|---|---|---|---|
| ZSFZ(B) 80-1.6 | 230 | 530 | 180 | 250 | 110 | 150 | 160 | 8-Φ18 | / |
| ZSFZ(B) 100-1.6 | 260 | 540 | 190 | 260 | 120 | 150 | 180 | 8-Φ18 | / |
| ZSFZ(B) 125-1.6 | 275 | 540 | 200 | 270 | 130 | 160 | 210 | 8-Φ18 | / |
| ZSFZ(B) 150-1.6 | 305 | 540 | 205 | 275 | 142.5 | 180 | 240 | 8-Φ22 | / |
| ZSFZ(B) 200-1.6 | 375 | 540 | 235 | 310 | 175 | 205 | 295 | 12-Φ22 | / |
| ZSFZ(B) 250-1.6 | 470 | 555 | 260 | 330 | 215 | 230 | 355 | 12-Φ28 | / |
| ZSFZ(B) 300-1.6 | 560 | 580 | 290 | 365 | 255 | 250 | 410 | 12-Φ28 | / |
| ZSFZ(B) 100-1.6G | 250 | 540 | 190 | 260 | 100 | 150 | / | / | 110.1 |
| ZSFZ(B) 150-1.6G | 305 | 545 | 215 | 285 | 140 | 150 | / | / | 160.8 |
| ZSFZ(B) 200-1.6G | 330 | 555 | 245 | 300 | 145 | 150 | / | / | 214.4 |
2.2 Alarm Flow Requirements (GB5135-2003)
| Inlet Pressure (MPa) | Minimum Alarm Flow (L/min) | Standard Required Alarm Flow (L/min) |
|---|---|---|
| 0.14 | 20 | 60 |
| 0.70 | 40 | 80 |
| 1.20 | 60 | 170 |
| 1.60 | 80 | 170 |
2.3 Key Parameters
Ambient Temperature Range: 4℃~70℃
Valve Type: Disc type one-way valve
Working Pressure Rating: 1.6 MPa
Core Accessories: Hydraulic alarm bell, pressure switch, delay device, pressure gauges (2 pcs)
Certifications: CCC, CE, GB50084-2017 compliant, GB5135-2003 compliant
3. Installation, Debugging & Maintenance Instructions
3.1 Installation Guidelines
Environment Requirement: Install in locations with ambient temperature 4℃~70℃, avoiding extreme conditions.
Pipeline Preparation: Install vertically on pressure-tested and flushed pipelines, ensuring correct water flow direction and sufficient maintenance space.
Pipeline Treatment: Thoroughly flush system pipelines and apply anti-rust coating to remove debris and prevent corrosion.
Drainage Connection: Connect each drainage outlet to the sewer with separate pipelines for unobstructed drainage.
Accessory Installation: Mount fire signal butterfly valves (matching caliber) at both ends for easy control and maintenance. Install the hydraulic alarm horizontally (small opening = water inlet) and vertically (large opening = drain outlet); position pressure gauges for clear reading.
3.2 Debugging Steps
Pre-Check: Confirm all accessories are correctly and completely installed.
Valve Position Setup: Open the outlet signal butterfly valve and alarm control valve (normally open); close the water test ball valve (normally closed) and drain valve (normally closed).
Water Injection: Slowly open the inlet signal butterfly valve, injecting pressure water ≥0.14MPa. The valve flap opens, and water flows to the delay device-triggering the pressure switch and hydraulic alarm within 5~90s.
Pressure Balance: Close the drain valve, continue opening the inlet butterfly valve until the valve's upper/lower chamber pressure balances (system working pressure). The alarm stops, and residual water in the delay device drains within 5 minutes.
Functional Tests:
Alarm Test: Open the terminal water test valve-hydraulic alarm, pressure switch, and water flow indicator should activate.
Pipeline Supply Test: Open the drain valve-stable large water flow indicates unobstructed pipelines.
Hydraulic Alarm Test: Close the alarm control valve, open the water test ball valve-pressure switch and alarm should activate continuously. Reset valves after testing.
3.3 Maintenance & Troubleshooting
3.3.1 Regular Maintenance
Check pressure gauge readings and for leaks monthly.
Clean valve disc rubber sealing surfaces, valve seat rings, and filter dirt regularly; replace rubber seals every 18 months (or if worn/aged).
Keep valve seat annular groove small holes unobstructed; clean the delay device and ensure throttling holes are not blocked.
3.3.2 Common Troubleshooting
Continuous Dripping from Delay Device Drain: Open/close the drain valve several times; if dripping persists, open the valve cover to clean foreign matter on the valve seat and re-debug.
Weak or No Alarm Sound: Check if the alarm hammer rotates flexibly; verify the delay device's throttling orifice plate is correctly installed (large orifice facing the delay device) and not blocked.
4. Packaging & Transportation
Our products are carefully packaged using export-standard wooden crates or wooden pallets to ensure safe transportation. This packaging method provides stability, prevents damage during handling, and guarantees that all items arrive at the customer's location in excellent condition.
5. Application Scenarios
Commercial Buildings: Hotels, shopping malls, cinemas, office buildings, and retail centers.
Public Facilities: Hospitals, schools, community centers, and railway stations.
Residential Buildings: High-rise apartments, villa complexes, and residential underground garages.
Industrial & Logistics: Warehouses, logistics centers, and light industrial workshops.
Infrastructure: Subway stations, underground passages, and public parking garages.
6. Frequently Asked Questions (FAQ)
Q: What is the ambient temperature range for this wet alarm valve?A: It is suitable for environments with temperatures between 4℃ and 70℃-avoid installing in freezing or overheated areas to prevent system malfunction.
Q: When does the alarm trigger?A: The alarm activates when the inlet pressure is 0.14MPa/0.70MPa/1.20MPa/1.60MPa and the system-side flow reaches 20L/min/40L/min/60L/min/80L/min (minimum) or the standard required flow (60L/min/80L/min/170L/min/170L/min).
Q: How often should the rubber seals be replaced?A: The service life of rubber seals is generally 18 months. We recommend replacement during annual maintenance to ensure sealing performance and prevent leaks.
Q: Can the valve be installed horizontally?A: No. The valve must be installed vertically to ensure proper operation of the valve flap and pressure difference activation.
Q: What standards does this product comply with?A: It complies with Chinese national standards GB50084-2017 and GB5135-2003, as well as international CCC and CE certifications, meeting global fire safety regulatory requirements.
7. Product Comparison Table (vs. Competitors)
| Comparison Item | Our ZSFZ(B) Type Wet Alarm Valve | Competitor A | Competitor B |
|---|---|---|---|
| Compliance Standards | GB50084-2017+GB5135-2003+CCC+CE | Only CE | No key certifications |
| Model Options | 10 models (80-300mm, G-series) | 5 models (100-200mm) | 3 models (100-150mm) |
| Alarm Sensitivity | Low minimum flow (20-80L/min) | Higher minimum flow (40-100L/min) | Unstable sensitivity (false alarms) |
| Head Loss | Small | Medium | Large |
| Rubber Seal Service Life | 18 months | 12 months | 6-8 months |
| Maintenance Cost (Annual) | $35/unit | $50/unit | $45/unit (frequent repairs) |
| After-Sales Warranty | 2 years + technical support | 1 year | No warranty |
| Core Accessories | Hydraulic alarm + pressure switch + delay device (included) | Pressure switch only | No included accessories |
8. Contact: Dulcia
Email: sales8@ca-fire.com
Tel/WhatsApp: +86 191 6381 1547 / +86 15985963342
WeChat: Dulcia8
Hot Tags: ca-fire zsfz(b) type wet alarm valve product, China ca-fire zsfz(b) type wet alarm valve product manufacturers, suppliers, factory
Send Inquiry