Wet Alarm Valve Sprinkler System

Wet Alarm Valve Sprinkler System

The wet alarm valve is a one-way valve that only allows water to flow into the sprinkler system in one direction and alarms at a specified flow rate. The wet alarm valve usually equals the water pressure before and after the valve disc (the water passes through the water pressure balance hole in the guide pipe to keep the water pressure balance before and after the valve disc).

Description

Ca-Fire Protection Co.,Ltd is one of the most credible manufacturers and suppliers of wet alarm valve sprinkler system in China. Welcome to wholesale custom made fire equipment products at competitive price from our factory. Contact us for more cheap products.

 

Wet Alarm Valve Sprinkler System

 

Working Principle

  1. The wet alarm valve is to rely on the reduction or elevation of the water pressure on the side of the pipe network system to open and close the valve disc.
  2. In standby mode, when the water supply pressure fluctuates slightly, the bypass balance pipe can balance the upper and lower water pressures of the valve disc, so that the upper pressure surface of the valve disc is greater than the lower pressure surface, so that the valve disc will not open and cause false alarms.
  3. When a fire occurs, the water pressure on the pipe network side decreases due to the water spray explosion, resulting in a pressure difference between the water supply side and the system side, causing the valve to open and the opened nozzle to continue to supply water.

 

The matters needing attention during installation and operation of the wet alarm valve are as follows.

  1. When installing the wet alarm valve, pay attention to the direction of the valve body. And carry out pipeline flushing before installation to avoid sedimentation of mud, sand and dirt, and to prevent blockage of the annular groove.
  2. During installation, if it is found that even if the wet alarm valve is closed, there is still water flowing out of the drain port of the delayer, indicating that the valve flap is not tightly sealed and should be checked, repaired or updated.
  3. The working status of the alarm system should be checked regularly. Generally, water can be discharged through the end test device of the automatic sprinkler system to confirm whether the pressure switch, hydraulic alarm bell and wet alarm valve are normally watered.
  4. Frequently check whether the pipeline system is blocked. The inspection method is: close the valve on the pipeline to the delayer and hydraulic alarm bell, and open the ball valve of the main drain pipe. If a large amount of water flows out, the pipeline is unobstructed.

 

Our Advantages

we are the experienced factory

we have many kinds of upvc window locks pvc sliding window lock crescent lock with hook for you choose

We can print your logo in our upvc window locks pvc sliding window lock crescent lock

We can customize the color accoring to your needs

We can do OEM &ODM

 

Our Service

> We provide free technical service about casting parts and application issues.

> Free on-site touring and introduction of our factory.

> We provide process design and validation for free.

> We can guarantee on-time delivery of samples and goods.

> Close follow-up of all orders by special person and keep customers informed timely.

 

about1 1
about1 2
about1 3
about1 4
about1 5
about1 6
FAQ

Q: WHAT IS YOUR MOQ ?

A: Usually our MOQ is 3,000pcs. But we accept lower quantity for your tria order. Please feel free to tell us how many pieces you need, we will calculate the cost correspondingly, hoping you can place large orders after checking quality of our products and know our service.

Q: HOW LONG IS THE SAMPLE LEAD TIME ?

A: For existing sample, it takes 2-3 days. They are free. If you want your own designs, it takes 7-10 days, subject to your designs whether they need new MOLD, etc. Anyway, we will response fast to your request.

Q: HOW LONG IS THE PRODUCTION LEAD TIME ?

A: It takes 35 days for MOQ. We have large production capacity, which can ensure fast delivery time even for bulk.

Q: WHAT FORMAT OF THE FILE DO YOU NEED IF I WANT MY OWN DESIGN ?

A: We have our own designer in house. So you can provide JPG, AI, cad or PDF, etc. We will make drawing for mold or printing screen for your final confirmation based on technique.

Q: WHAT IS YOUR PAYMENT TERM ?

A: Our payment is TT 30% deposite and 70% against bill of loading copy of TT. PayPal, Western&Union.

Hot Tags: wet alarm valve sprinkler system, China wet alarm valve sprinkler system manufacturers, suppliers, factory, Wet Alarm Valves, Reliable Wet Alarm Valve

You Might Also Like

Shopping Bags